 1012B/2012B Direct-Wire Smoke Detector with Built-in Relay and Horn
A Division of Pittway 3825 Ohio Avenue, St. Charles, IL 60174 1-800-SENSOR2 (736-7672), Fax 630-377-6495 http://www.systemsensor.com
Models Available
1012B Ionization Detector 2012B Photoelectronic Detector
Features
* 12 VDC operation, 4-wire * Built-in 85dB electronic horn * Built-in relay can be connected to lights, bells, horns, remote annunciator, or control panel * Interconnectable up to 12 units * Visual alarm and power indicator * Ceiling white color * Built-in 8 second delay on relay output * Built-in test switch * Twist-on mounting bracket with tamper option for easy installation * Improved chamber design for greater stability * Same housing design for both ion and photo models * 3-year warranty Compact, attractive, and easy to install, System Sensor 1012B and 2012B detectors are designed to respond to a broad range of fires while providing maximum stability. Both units in this series feature low-voltage wiring, allowing you to choose the detector that best suits your application.
Specifications
Size: Weight: Humidity Range: 1.75 h x 5.5 dia. (44.5 mm h x 140 mm dia.) 5.3 oz. (150 grams) 10% to 93% RH, noncondensing Smoke Detector Spacing: On smooth ceilings (as defined in NFPA 72), spacing of 30 feet (900 sq. ft.) may be used as a guideline. Other spacing may be used depending on ceiling height, high air movements, and other conditions or response requirements.
Electrical Ratings
Operating Voltage: Relay Contact Rating: Standby Current: Alarm Current: Temperature Range: 12 VDC (nominal) 1 Form A, .5 A @ 30 VDC 50 A maximum average 20 mA maximum average @ 12 VDC 32 to 120F (0 to 50 C)
(c) System Sensor 8/96
This document is not intended to be used for installation purposes.
A05-238-02
General Description
System Sensor 1012B ionization and 2012B photoelectronic detectors are designed primarily for applications where low-voltage Class 2 wiring may be used. These detectors are self-resetting and offer an 85dB alarm horn. An external push button provides a test of the detectors' alarm function. Up to 12 units can be interconnected so that if one detector alarms, all detectors alarm. A normally open auxiliary alarm relay is available for controlling external functions. A visible LED indicator flashes once every 40 seconds in standby and rapidly in alarm when detecting smoke. The detectors offer low-voltage operation and a tamper-proof feature. Screw terminals and a mounting bracket are provided for easy installation.
RED (+) A77-727-O1 GRAY (-)
BLACK
12VDC POWER 12OVAC BLACK SUPPLY
POWERS UP TO 16 DETECTORS
GROUND SIGNAL GROUND SIGNAL
(+) (-) POWER INPUT (+) (-) POWER INPUT (+) (-) POWER INPUT
AUXILIARY
AUXILIARY
AUXILIARY
GROUND SIGNAL
GROUND SIGNAL
(+) (-) POWER INPUT
(+) (-) POWER INPUT
(+) (-) POWER INPUT
GROUND SIGNAL
GROUND SIGNAL
AUXILIARY ALARM RELAY
AUXILIARY AUXILIARY AUXILIARY
INTERCONNECT UP TO 12 DETECTORS
WIRE GAUGE 1 UNIT 2 UNITS 3 UNITS 4 UNITS 5 UNITS 6 UNITS 7 UNITS 8 UNITS 9 UNITS 10 UNITS 11 UNITS 12 UNITS 14AWG 5000 990 848 742 660 594 540 495 2970 1980 1485 1188 16AWG 3735 622 533 466 415 373 339 311 1867 1245 933 747 18AWG 2349 391 335 293 261 234 213 195 1174 783 587 469 MAXIMUM POWER BUS LENGTH IN FEET. GIVEN NUMBER OF UNITS (MAXIMUM PER BUS) AND WIRE SIZE. MAXIMUM INTERCONNECT BUS LENGTH: 5,000 FT. NO. 18AWG OR LARGER DUAL CONDUCTOR CABLE. ALL WIRING MUST CONFORM TO LOCAL ELECTRICAL CODES. RELAY CONTACTS RATING: 0.5A 30VDC; 0.5A 30VAC
1012B/2012B Wiring Diagram
Ordering Information
Part No. 1012B 2012B Description Ionization smoke detector with relay, 12 VDC, multiple station Photoelectronic smoke detector with relay, 12 VDC, multiple station A77-727-01 12 VDC power supply, mounts to a 4 square box, 21 /8 deep
System Sensor Worldwide Distribution
In Canada: System Sensor Canada 6581 Kitimat Road, Unit #7 Mississauga, Ontario Canada L5N 3T5 Telephone: 905-812-0767 Fax: 905-812-0771 Page 2 In the United Kingdom: System Sensor Europe, Ltd. Horsham Gates III, North St. Horsham, West Sussex RH13 5PJ, United Kingdom Telephone: 44-1403-276500 Fax: 44-1403-276501 In India: System Sensor India A-204 Maheshwari Nagar Orkay Mills Lane Andheri East, Mumbai 400093 Telefax: 91-022-8202564 In the Far East: System Sensor Pittway Far East, Ltd. Suite 706, New T&T Centre 7 Canton Road Tsimshatsui, Kowloon, Hong Kong Telephone: 852-2730-9090 Fax: 852-2736-6580 A05-238-02


▲Up To Search▲   

 
Price & Availability of 2012B

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X